Recording trends, spectra and dynamic data makes it possible to spot changes in machine behaviour earlier and to plan maintenance better.
Scope
What we offer
We match the monitoring architecture to machine criticality and the plant's infrastructure — from systems for turbine-generator sets to solutions for auxiliary machinery. We work with Emerson, Bently Nevada, Parker Meggitt and other manufacturers' systems.
- Architecture and measurement point selection
- Sensors and measurement chains
- Diagnostic software and data analysis
- Integration with DCS / SCADA
- Wireless monitoring of auxiliary machinery
- Commissioning and staff training
Who it's for
When online monitoring pays off
Critical machinery
A failure means a production stop.
Periodic checks fall short
Faults develop faster than the measurement cycle.
Difficult access
Machines in hazardous or hard-to-reach areas.
Legacy system
Vendor support has ended and spare parts are unavailable.
No diagnostic data
The existing system only raises alarms, with no analysis.
Many auxiliary machines
A need for centralised supervision.
Recognise one of these symptoms? An analyst will help find the cause.
Architecture
What the system includes
Measurement layer
Vibration, position and speed sensors.
Monitoring modules
Signal acquisition and processing.
Software
Trends, spectra, alarms and diagnostic analysis.
Integration
Data exchange with DCS, SCADA and plant systems.
Process
How we work together
- 01
Audit
Machines, existing infrastructure, requirements.
- 02
Concept
Architecture and system selection.
- 03
Supply and installation
Sensors, cabinets, cabling.
- 04
Commissioning
Configuration, testing, integration.
- 05
Support
Training, service, data analysis.
Projects
Related projects
2026
AB Achema, Jonava · Lithuania
Supply of a new Orbit 60 protection and vibration monitoring system.
2026
Dunamenti Erőmű, Százhalombatta · Hungary
Supply, installation and commissioning of an Orbit 60 monitoring system.
2026
TAURON, Nowe Jaworzno power plant · Poland
Pump monitoring on the 910 MW unit upgraded: Orbit 60 supplied, installed, configured and commissioned on feed pumps.
2025–2026
ANWIL, Włocławek · Poland
Bently Nevada machinery monitoring system with sensors for 9 machines: 3 fans and 6 pumps.
2025
Grupa Azoty, Tarnów · Poland
Bently Nevada machinery monitoring system for a HOWDEN reciprocating compressor: equipment, works and services.
2025
Rafineria Gdańska, Gdańsk refinery · Poland
Upgrade of the machinery monitoring system for the pump units P8A+P1A and P8B+P1B at Unit 100.
2025
ORLEN Lietuva, Mažeikiai refinery · Lithuania
Protection, vibration monitoring and diagnostics for reciprocating compressors SK-301 and SK-302 in compressor house LK-2.
2025
ORLEN, Płock refinery · Poland
Orbit 60 monitoring and protection system supplied for turbines TG4 and TG5.
Related services
Typical machines
Other rotating machinery — e.g. wind turbines, gearboxes. Ask us →
Frequently asked questions
Didn't find your answer? Ask an engineer →
Which vibration monitoring and machinery protection systems does Energomechanika offer?
Energomechanika supplies and implements Emerson condition monitoring solutions and machinery protection systems for rotating machinery. A project can include selecting vibration sensors, configuring the equipment, commissioning and integration with the plant's control systems. We also provide independent technical support for Bently Nevada, Parker Meggitt and other systems in service, to the extent the specific configuration allows.
Can a vibration monitoring system be integrated with a DCS or SCADA?
Yes. Machine monitoring systems can make measured values, statuses, alarms and selected diagnostic data available to a DCS or SCADA. Integration uses the interfaces provided by the equipment manufacturers, such as Modbus or OPC UA. We define the scope of data exchange after reviewing the system architecture and the control and cybersecurity requirements.
What is the difference between condition monitoring and a machinery protection system?
Condition monitoring is used to observe vibration, analyse trends and detect developing faults. A machinery protection system, on the other hand, performs defined protective functions, such as raising an alarm or tripping the machine when set thresholds are reached. Both can use the same measurement data, but they differ in their functional requirements and in how they are designed.
Can the existing vibration sensors be kept when a monitoring system is upgraded?
Often yes, but this requires an assessment of technical compatibility. Before an upgrade, we check the sensor types, their characteristics, power supply, cabling, measurement channel configuration and the requirements of the new monitoring or protection system. Existing parts of the installation can be retained only if this does not degrade measurement quality or the required functionality.
Can vibration monitoring predict a machine failure?
Online monitoring can detect the symptoms of a developing fault before it leads to a machine outage. Analysis of vibration trends and their relationship to operating conditions is particularly important. Not every failure can be predicted, however, and how effective early detection is depends on the type of fault, the sensor locations and the system configuration.
Does a machine monitoring system have to be connected to the internet?
No. A vibration monitoring or protection system can operate on a local industrial network without a permanent internet connection. How data is archived and shared, and whether any remote access is provided, is decided according to the user's requirements and the plant's cybersecurity policy.
Does installing online monitoring require a machine shutdown?
Not all of the work requires a shutdown. Preparing cabinets, configuring software and part of the DCS integration can often be done while the machine is in operation. However, installing certain vibration sensors, changing cabling or working on the existing protection system may require the machine to be safely stopped. We agree the schedule after a technical assessment of the installation.
When is it worth implementing an online vibration monitoring system?
Online vibration monitoring is particularly justified for critical machines whose unplanned outage causes high losses or process hazards. It provides continuous recording of parameters, trend analysis and faster detection of abnormalities. The choice of system depends on the machine's design, the diagnostic functions required and the existing protection system. Not every installation needs equally extensive monitoring, however.
How do you select a monitoring and protection system for a turbine or compressor?
Selection starts with an analysis of the machine, its criticality, its bearings and the measurement parameters required. Turbines and compressors may need sensors for shaft vibration, bearing housing vibration, axial position and rotational speed. Diagnostic, alarm and trip functions are defined separately. The design must take into account the machine manufacturer's requirements, the applicable standards and the plant's control system architecture.
Which vibration sensors are used on rotating machinery?
Rotating machinery diagnostics uses accelerometers, velocity sensors and non-contact shaft displacement probes, often based on the eddy-current principle, among others. The choice depends on the frequency of the phenomena, the bearing type and the measurement location. Monitoring and protection systems also use axial position and speed sensors. Not every sensor can be swapped without changes to the measurement chain.
How does an eddy-current probe differ from an accelerometer and a velocity sensor?
An eddy-current probe measures, without contact, the change in distance between the probe and a conductive target, which is why it is used to measure relative shaft vibration, among other things. An accelerometer measures vibration acceleration, and a velocity sensor measures vibration velocity, of the component it is mounted on. Each technique has a different range of applications and different mounting requirements. The choice follows from the machine's design and the purpose of the monitoring.
How should vibration alarm and trip thresholds be set?
Alarm and trip thresholds are set on the basis of the machine manufacturer's requirements, the relevant standards, operating data and a risk analysis. The type of measurement, the sensor location and the machine's duty, including start-up conditions, all matter. Protection system setpoints should not simply copy general vibration evaluation zones. Their approval and testing must follow the plant's procedures.
What does API 670 require of machinery protection systems?
API 670 applies to machinery protection systems used in demanding industrial installations. Depending on the configuration, it covers selected measurements related to vibration, axial position and rotational speed, as well as system functions. In design, its requirements for measurement channels, reliability, alarms and testing are important. A specific solution should be checked against the agreed edition of the standard and the project specification.
How is a turbine protected against overspeed?
Turbine overspeed protection is designed to prevent operation above the permissible speed by detecting when a set threshold is exceeded and initiating a trip. Depending on the machine's requirements, the system may use independent speed measurement channels and suitably designed logic. Correct sensor selection, verification of the setpoints and periodic testing of the complete protective function are essential.
When should a machinery monitoring and protection system be upgraded?
An upgrade is worth considering when spare parts for the existing system are hard to obtain, or when it does not provide the required measurements, makes diagnostics difficult or does not meet the plant's current requirements. We assess the condition of the sensors, cabling, modules, communications and protection functions. In many cases an upgrade can be carried out in stages, but keeping existing components requires confirmation of technical compatibility and operational safety.
How do you verify that the measurement channels of a protection system work correctly?
Verifying a measurement channel covers the sensor, cabling, signal processing and configuration, as well as the transmission of alarm and trip signals. Testing should cover the required functions from input to output, in line with the documentation and the plant's procedures. In machinery protection systems, reading a correct value on the screen is not enough: what matters is confirming that the whole channel works.
Can vibration monitoring support predictive maintenance?
Yes. Analysing vibration trends, spectra and process data helps detect developing abnormalities and plan diagnostics or an overhaul at a convenient time. Online monitoring provides regular data, but it does not replace the interpretation of that data or knowledge of the machine's design. Predictive maintenance works best when measurement data is linked to the fault history and to service planning.
Need a diagnosis or a quote?
Basic machine data and a short description are enough.